Production process guidance
1. Workers strictly follow the construction drawings of electrical engineers and structural engineers of the design center (notice the workshop director for special circumstances or objections to assist in solving). 2. When sealing the lower end of the dual power supply, if there are more than 3 conductors on the load side, the voltage is divided on both sides (except for special cases). 3. A: The crimping line at the lower end of the micro-break switch is crimped up to 35 mm². When there are multiple lower ends, up to 5 wires (2.5 to 4 mm² wire) are crimped per phase; when multiple 6 mm² wires are crimped, a maximum of 4 single-phase crimped wires (except for household boxes). When there are multiple 10 mm² conductors, a maximum of 2 single-phase crimps are used; when the above requirements are exceeded, copper bar transfer is performed. B: The outlet of the lower end of the molded case switch, when there are multiple crimping (2.5 ~ 6 mm² specification wire) no more than 50 mm wiring...